We review your drawings, ratings and site fault current, or prepare the drawings ourselves.
WETS AI builds UL 508A industrial control panels in our Houston, Texas shop. Every panel is built to the standard, checked for its SCCR marking, nameplate and warning labels, and fully tested before it carries the UL mark and ships to customers across the United States and Canada.
UL 508A is the UL standard for industrial control panels. It sets the rules for how a panel is put together: which components can be used and within which ratings, how wiring is sized and spaced, how the panel is grounded, and what has to be marked on it.
A panel built and labeled in a UL 508A shop shows that the whole assembly, not just the parts inside it, was built and checked to the standard. Inspectors, insurers and plant owners use that label to accept a panel without extra field review, which is why many specifications require it.
For you, the label means fewer questions at inspection and a panel that is documented the same way every time.

The label is the last step, not the first. These are the points we confirm before any panel is marked.
| Check | Why it matters |
|---|---|
| Components are suitable and used within their ratings | The standard only allows parts used the way their own ratings allow. |
| Short-circuit current rating (SCCR) is calculated | The panel must be able to withstand the fault current available where it is installed. |
| Wire size, type and color match the drawings | Correct conductors carry the load safely and make the panel easier to maintain. |
| Spacing and routing are correct | Power and control wiring stay apart and away from sharp edges and heat. |
| Ground and bond connections are complete | Every metal part that could become live is tied to ground. |
| Nameplate, warning labels and field-wiring terminals are marked | Installers and inspectors get the information they need without opening the drawings. |
The full list of checks, including electrical and functional tests, is on our testing page.
Every UL 508A panel leaves our shop with a nameplate that carries the information installers and inspectors need.
The short-circuit current rating is the highest fault current the panel can safely withstand. Electrical codes require it to be marked on industrial control panels, and the marked value has to be at least the fault current available at the point where the panel is connected.
Under UL 508A, the panel SCCR is set by the weakest component in the power circuit, unless current-limiting devices are used to raise it. That is why the rating has to be designed in, not checked at the end.
Tell us the available fault current at your site early. We then select breakers, fuses, starters and drives that reach the rating you need, and show the result on the nameplate.
A panel is only as strong as its lowest-rated part in the power circuit, unless a current-limiting device protects that part.
We review your drawings, ratings and site fault current, or prepare the drawings ourselves.
Components are chosen or verified against UL 508A and the SCCR target.
The panel is assembled, wired, marked and inspected against the drawings.
Electrical and functional tests are completed, then the UL mark is applied.
We mostly build in these NEMA enclosure types. The right one depends on where the panel will live.
Usually not as it stands. The UL 508A label covers how the whole panel was built, so we can only apply it to panels we build, or rework completely, in our own shop. Send us the drawings and photos and we will tell you which option fits.
The electrical schematics, the bill of materials with part numbers, and the available fault current at the point where the panel will be connected. Your electrical engineer or utility can usually provide the fault current.
Yes. Every panel passes 13 checks covering the build, electrical tests and functional tests before the label is applied.
Mostly NEMA 1 for clean indoor rooms, NEMA 3R for outdoor sites, NEMA 4 for hose-down areas and NEMA 4X where corrosion is a concern. Tell us where the panel will be installed and we will recommend a rating.
About 16 weeks on average from order to shipment. The real figure depends on panel size and on component lead times, so we confirm a schedule with every quotation.
The 13 checks every panel passes, plus witnessed FAT and SAT on site.
Your drawings and bill of materials, built, marked and tested to UL 508A.
Controllers, I/O, networks and power, built to UL 508A and tested point by point.
Send us your drawings, or a description of the process, and we will come back with a clear quotation and schedule.