VFD Control Panels
Drives, bypass, reactors and cooling for pumps, blowers and fans.
A variable frequency drive turns roughly 2 to 3 percent of the power it handles into heat, and in a closed panel that heat has to go somewhere. A 50 hp drive can give off around a kilowatt at full load. Clean indoor rooms can use filter fans, sealed outdoor panels need an air-to-air heat exchanger or an enclosure air conditioner, and the choice depends on the heat load, the enclosure type and the hottest day on site.
The right method depends on two things: whether the enclosure must stay sealed, and how hot the air outside the panel gets.
A quick first estimate before the detailed calculation. Use the drive manufacturer's published losses for the final design.
| Drive size | Approx. heat at full load |
|---|---|
| 5 hp | About 100 W |
| 15 hp | About 300 W |
| 50 hp | About 1,000 W |
| 100 hp | About 2,000 W |
Approximate, based on 2 to 3 percent losses. Add heat from power supplies, transformers, PLCs and the sun on the enclosure.

Drives and their electronics are rated for a maximum surrounding air temperature. Above it, drives derate, trip on overtemperature or simply fail sooner. A panel that runs fine in spring can trip every afternoon in August.
Placement inside the panel matters too. We mount drives so their own cooling air flows freely, keep heat-sensitive parts away from the hot air above them, and leave the clearances the manufacturer asks for.
An enclosure in direct sun picks up heat through its walls, on top of what the drives produce. A sunshield, a light color and a location on the shaded side of equipment all help.
For sealed NEMA 4 or 4X panels outdoors in Texas, an enclosure air conditioner is often the only option that keeps the inside cooler than the summer air outside.

Some drives are made for wall mounting or have a through-panel heat sink, which puts most of the heat outside the enclosure. It depends on the drive and the location.
Not without losing the rating, because the openings break the seal. Use an air-to-air heat exchanger or an air conditioner rated for the enclosure type.
It depends on the components, but many drives and PLCs are rated for around 40 to 50°C surrounding air. Check each component's rating.
Yes. We work out the heat load from the components and the site conditions and choose the cooling method as part of the design.